This FAQ has been written for NEAL (North East Africa and Levant) region. If you are looking for information for another region, please select the correct country from the top-left dropdown in the page and 'Navigate to Browse FAQs' in the Support menu.
Description:
Meaning of Easergy Micom P642 is showing “ AutoLZREF sf OOR” in the evens.
Product family: Easergy Micom P642
Resolution:
It means that Scaling factor of autotransformer low impedance REF is out of range.