Issue:
Protocol setting (PRP/RSTP etc.) in Micom Px4x relays through Easergy studio
Environment/Product line:
Micom P14x relay
Resolution :
Protocol setting has to be selected in relay's front display and it not possible via Easergy Studio software.
So you have to select through relay’s front display then retrieve the information into EasergyStudio.
After that you can extract setting and able to see the require setting of your device.
Protocol setting (PRP/RSTP etc.) in Micom Px4x relays through Easergy studio
Environment/Product line:
Micom P14x relay
Resolution :
Protocol setting has to be selected in relay's front display and it not possible via Easergy Studio software.
So you have to select through relay’s front display then retrieve the information into EasergyStudio.
After that you can extract setting and able to see the require setting of your device.
Released for: Schneider Electric Egypt and North East Africa