V221-Slave mode installation
Issue
In application of multiple central units in Arc system, the error code XX-10 always appeared on Slave mode V221 even after execution of install command and Error reappeared again after few minutes from clearing error code on Slave mode V221.
_____________________________________________________________
Product Line

Arc protection relay
_____________________________________________________________

Environment
N/A
_____________________________________________________________
Root Cause
Customer didn’t follow the instruction in our V221 manual.
_____________________________________________________________
Solution
We have to follow the instruction in our V221 manual as shown in below screenshot.

1

1

_____________________________________________________________

 =====End of document=====
 
 

Schneider Electric Egypt and North East Africa

Users group

Discuss this topic with experts

Visit our community and get advice from experts and peers on this topic and more

Need help?

  • Start here!

    Find answers now. Search for a solution on your own, or connect with one of our experts.

  • Contact Support

    Reach out to our customer care team to receive more information, technical support, assistance with complaints and more.

  • Where to buy?

    Easily find the nearest Schneider Electric distributor in your location.

  • Search FAQs

    Search topic-related frequently asked questions to find answers you need.

  • Contact Sales

    Start your sales inquiry online and an expert will connect with you.

  • Products Documentation
  • Software Downloads
  • Product Selector
  • Product Substitution and Replacement
  • Help and Contact Center
  • Find our Offices
  • Get a Quote
  • Where to buy
  • Careers
  • Company Profile
  • Report a misconduct
  • Accessibility
  • Newsroom
  • Investors
  • EcoStruxure
  • Job Search
  • Blog
  • Privacy Policy
  • Cookie Notice
  • Terms of use
  • Change your cookie settings
Your browser is out of date and has known security issues.

It also may not display all features of this website or other websites.

Please upgrade your browser to access all of the features of this website.

Latest version for Google Chrome, Mozilla Firefox or Microsoft Edgeis recommended for optimal functionality.