Issue:
For 115v input ATV12 drives, what should the UnS parameter be set at?
Product Line:
ATV12
Environment:
115v input
Cause:
n/a
Resolution:
If the Line voltage is less than the rated motor voltage, the rated motor voltage should
be set to the value of the line voltage, applied to the terminals.