Problem: The self-test status of SRTG UPS models reports "Refused" after a successful self-test
Product Line: UPS models with the prefix SRTG
Cause: Due to the current firmware logic, it is expected behavior that SRTG UPS models report "Refused" after a successful self-test. The expected self-test status sequence is Status: In Progress -> Actual self-test screen -> Status: Refused, as shown below:
->
->
Resolution: A future firmware update will improve the UPS self-test reporting.
Released for: Schneider Electric Egypt and North East Africa
Need help?
Product Selector
Quickly and easily find the right products and accessories for your applications.
Get a Quote
Start your sales enquiry online and an expert will connect with you.
Where to buy?
Easily find the nearest Schneider Electric distributor in your location.
Help Center
Find support resources for all your needs, in one place.