Egypt and North East Africa (English)

Welcome to the Schneider Electric Website

Welcome to our website.

You can choose another country to view available products or go to our Global website for company information.

Choose another country or region

TM3TI8T Product picture Schneider Electric

View all Modicon TM3

Modicon TM3 - TM3TI8T

Analog I/Os

TM3TI8T Product picture Schneider Electric
View all Modicon TM3
Modicon TM3 - TM3TI8T
Analog I/Os

module TM3 - 8 inputs temperature

Show more characteristics >
Add to My Products Remove from My Products

  • Main
    range of product
    Modicon TM3
    product or component type
    Analog input module
    range compatibility
    Modicon M221
    Modicon M241
    Modicon M251
    analogue input number
    8
    analogue input type
    Thermocouple, analogue input range: - 200...1000 °C with thermocouple J
    Thermocouple, analogue input range: - 200...1300 °C with thermocouple K
    Thermocouple, analogue input range: 0...1760 °C with thermocouple R
    Thermocouple, analogue input range: 0...1760 °C with thermocouple S
    Thermocouple, analogue input range: 0...1820 °C with thermocouple B
    Thermocouple, analogue input range: - 200...400 °C with thermocouple T
    Thermocouple, analogue input range: - 200...1300 °C with thermocouple N
    Thermocouple, analogue input range: - 200...800 °C with thermocouple E
    Thermocouple, analogue input range: 0...2315 °C with thermocouple C
    NTC 10k thermistor, analogue input range: -90...150 °C
    PTC thermistor, analogue input range: 100...10000 Ohm
    Thermocouple, analogue input range: - 200...1000 °C
    Complementary
    analogue input resolution
    15 bits + sign
    16 bits
    input impedance
    >= 1 MOhm temperature probe
    >= 1 MOhm thermistor
    >= 1 MOhm thermocouple
    LSB value
    0.1 °C with NTC probe
    1 Ohm with PTC/NTC probe
    0.1 °C thermocouple
    conversion time
    100 ms + 100 ms per channel + 1 controller cycle time
    sampling duration
    100 ms
    absolute accuracy error
    +/- 0.2 % of full scale at 25 °C for thermocouple C 0...2315 °C
    +/- 6 °C at 25 °C for thermocouple R, S 0...200 °C
    +/- 0.2 % of full scale at 25 °C for thermocouple R, S 200...1760 °C
    +/- 0.2 % of full scale at 25 °C for thermocouple B 300...1820 °C
    +/- 0.4 % of full scale at 25 °C for thermocouple K - 200...0 °C
    +/- 0.2 % of full scale at 25 °C for thermocouple K 0...1300 °C
    +/- 0.4 % of full scale at 25 °C for thermocouple J - 200...0 °C
    +/- 0.2 % of full scale at 25 °C for thermocouple J 0...1000 °C
    +/- 0.4 % of full scale at 25 °C for thermocouple E - 200...0 °C
    +/- 0.2 % of full scale at 25 °C for thermocouple E 0...800 °C
    +/- 0.4 % of full scale at 25 °C for thermocouple T - 200...0 °C
    +/- 0.2 % of full scale at 25 °C for thermocouple T 0...400 °C
    +/- 0.4 % of full scale at 25 °C for thermocouple N - 200...0 °C
    +/- 0.2 % of full scale at 25 °C for thermocouple N 0...1300 °C
    temperature drift
    +/- 0.01 %FS/°C
    repeat accuracy
    +/-0.5 %FS
    non-linearity
    +/- 0.2 %FS
    cross talk
    <= 1 LSB
    [Us] rated supply voltage
    24 V DC
    supply voltage limits
    20.4...28.8 V
    type of cable
    Twisted shielded pairs cable 30 m for input circuit
    current consumption
    30 mA at 24 V DC via external supply
    45 mA at 5 V DC via bus connector
    40 mA at 5 V DC via bus connector
    local signalling
    1 LED green for PWR
    electrical connection
    10 x 1.5 mm² removable screw terminal block with pitch 3.81 mm adjustment for inputs and supply
    10 x 1.5 mm² removable screw terminal block with pitch 3.81 mm adjustment for inputs
    insulation
    500 V AC between input and internal logic
    1500 V AC between input and supply
    marking
    CE
    surge withstand
    1 kV for power supply with common mode protection conforming to EN/IEC 61000-4-5
    0.5 kV for power supply with differential mode protection conforming to EN/IEC 61000-4-5
    1 kV for input with common mode protection conforming to EN/IEC 61000-4-5
    mounting support
    Top hat type TH35-15 rail conforming to IEC 60715
    Top hat type TH35-7.5 rail conforming to IEC 60715
    Plate or panel with fixing kit
    height
    90 mm
    depth
    70 mm
    width
    23.6 mm
    product weight
    0.11 kg
    Environment
    standards
    EN/IEC 61131-2
    EN/IEC 61010-2-201
    resistance to electrostatic discharge
    4 kV on contact conforming to EN/IEC 61000-4-2
    8 kV in air conforming to EN/IEC 61000-4-2
    resistance to electromagnetic fields
    10 V/m at 80 MHz...1 GHz conforming to EN/IEC 61000-4-3
    3 V/m at 1.4 GHz...2 GHz conforming to EN/IEC 61000-4-3
    1 V/m at 2 GHz...3 GHz conforming to EN/IEC 61000-4-3
    resistance to magnetic fields
    30 A/m conforming to EN/IEC 61000-4-8
    resistance to fast transients
    1 kV I/O conforming to EN/IEC 61000-4-4
    resistance to conducted disturbances
    10 V at 0.15...80 MHz conforming to EN/IEC 61000-4-6
    3 V at spot frequency (2, 3, 4, 6.2, 8.2, 12.6, 16.5, 18.8, 22, 25 MHz) conforming to Marine specification (LR, ABS, DNV, GL)
    electromagnetic emission
    Radiated emissions, test level: 40 dBμV/m QP class A (10 m at 30...230 MHz) conforming to EN/IEC 55011
    Radiated emissions, test level: 47 dBμV/m QP class A (10 m at 230...1000 MHz) conforming to EN/IEC 55011
    immunity to microbreaks
    10 ms
    ambient air temperature for operation
    -10...55 °C (horizontal installation)
    -10...35 °C (vertical installation)
    ambient air temperature for storage
    -25...70 °C
    relative humidity
    10...95 % without condensation in operation
    10...95 % without condensation in storage
    IP degree of protection
    IP20
    pollution degree
    2
    operating altitude
    0...2000 m
    storage altitude
    0...3000 m
    vibration resistance
    3.5 mm at 5...8.4 Hz with DIN rail mounting support
    3 gn at 8.4...150 Hz with DIN rail mounting support
    shock resistance
    15 gn during 11 ms
    Offer Sustainability
    Sustainable offer status
    Green Premium product
    RoHS (date code: YYWW)
    REACh
    Product environmental profile
    Product end of life instructions
  • Documents & Downloads

    Language
    • English
    Catalogue
    Date
    Size
    Add to My Documents
    Date 5/2/18
    Size 3.8 MB
    User guide
    Date
    Size
    Add to My Documents
    Date 8/20/18
    Size 9.1 MB
    Date 5/23/18
    Size 8.2 MB
    Date 5/23/18
    Size 7.7 MB
    Date 5/23/18
    Size 1.3 MB
    Date 5/23/18
    Size 7.9 MB
    Date 5/23/18
    Size 2 MB
    Date 5/23/18
    Size 2.7 MB
    Date 3/1/18
    Size 6.9 MB
    CAD
    Date
    Size
    Add to My Documents
    Date 10/19/15
    Size 14 MB
    Date 7/21/16
    Size 15.2 MB
    Date 12/24/15
    Size 17.6 MB
    Date 12/24/15
    Size 16.3 MB
    Certificate
    Date
    Size
    Add to My Documents
    Date 9/12/17
    Size 213.5 KB
    Instruction sheet
    Date
    Size
    Add to My Documents
    Date 9/12/17
    Size 3 MB
    Declaration of conformity
    Date
    Size
    Add to My Documents
    Date 7/21/17
    Size 285.5 KB
    Date 9/24/17
    Size 565.5 KB
    End of life manual
    Date
    Size
    Add to My Documents
    Marine certificate
    Date
    Size
    Add to My Documents
    Date 9/24/17
    Size 171.3 KB
    Date 10/18/16
    Size 1.5 MB
    Date 7/12/17
    Size 218.1 KB
    Product environmental
    Date
    Size
    Add to My Documents
    REACh Declaration
    Date
    Size
    Add to My Documents
    Date 10/24/18
    Size 0
    RoHs Declaration
    Date
    Size
    Add to My Documents
    Date 10/24/18
    Size 0
  • Technical FAQs

    No results found
    Unfortunately, related FAQs are unavailable due to temporary technical issues. Please try again later.
  • Dimensions Drawings

    Dimensions


    (*)
    8.5 mm/0.33 in when the clamp is pulled out.


  • Mounting and Clearance

    Spacing Requirements



    Mounting on a Rail


    Incorrect Mounting



    Mounting on a Panel Surface


    (1)
    Install a mounting strip

    Mounting Hole Layout



  • Connections and Schema

    Analogue Input Module
    Wiring Diagram (Thermocouple Input Type)


    (*)
    Type T fuse
    (1)
    Thermocouple

    Wiring Diagram (Temperature Probe Input Type)


    (*)
    Type T fuse