APC Schneider Cooling Unit Identification

Article available in these languages: Spanish

Issue:
APC Cooling Unit identification.

Product line:
All Cooling Units.

Environment:
All Product models, all serial numbers.

Cause:
Nomenclature.

Resolution:

APC Unit Identification

FM Air/Water/Glycol
FMXXX-XXX-XXX
ModelCapacity KWModuleConfigurationVoltageReheatHumidifierAir Pattern
FM35 (10T)

40 (12T)

50 (15T)
M= Main

E= Expansion
A= Air Cooled

E= Air Cooled
w/Multicool

W= Water Cooled

F= Water Cooled
w/Multicool

D= Water Cooled
w/Economizer

G= Glycol Cooled

B= Glycol Cooled
w/Multicool

P= Glycol Cooled
w/Economizer
BA=208-230/3/60

KA= 480/3/60

MA= 600/3/60
E= Electric

W= Hot Water

S= Steam

H= Hot Gas

B= Hot Gas &
Electric

X= No Reheat
S=Replaceable
Steam Canister

C=Cleanable
Steam Canister

X=No Humidifier
D=Downflow

U=Upflow
(Front Return)

R=Upflow
(Rear Return)
FM-CW
FM40X-CXX-XXX
ModelCapacity KWModuleConfigurationVoltageReheatHumidifierAir Pattern
FM40 (12T)
A= 3 row 20
Circuit coil

B= 4 row 20
Circuit coil

C= 4 row 40
Circuit coil
C= Chilled Water

BA=208-230/3/60

KA= 480/3/60

MA= 600/3/60

AA=208/208/3/60

CA=480/208/3/60

DA=480/480/3/60

EA=600/208/3/60
F= Electric
(High Output)

X= No Reheat
S= Replaceable
Steam Canister

C= Cleanable
Steam Canister

X= No Humidifier
D= Downflow

U= Upflow
(Front Return)

R= Upflow
(Rear Return)

IR
IR40-CXX-XXX
FM40M-CXX-XXX
ModelCapacity KWConfigurationVoltageReheatHumidifierAir Pattern
IR40 (12T)
C= Chilled Water

MA= 600/3/60

AA=208/208/3/60

CA=480/208/3/60

DA=480/480/3/60

EA=600/208/3/60
E= Electric

X= No Reheat
S= Steam Canister

X= No Humidifier
A= In-Row
ModelCapacity KWModuleConfigurationVoltageReheatHumidifierAir Pattern
FM40 (12T)
M= MainC= Chilled Water

MA= 600/3/60

AA=208/208/3/60

CA=480/208/3/60

DA=480/480/3/60

EA=600/208/3/60
E= Electric

X= No Reheat
S= Steam Canister

X= No Humidifier
A= In-Row

AFX (Not Current)
AFX-XXXM-XX-XXX
ModelCapacity KWModuleConfigurationVoltageReheatHumidifierAir Pattern
AFX018 (5T)

065 (18T)
M= MainA= Air Cooled

W= Water Cooled

G= Glycol Cooled
BA=208-230/3/60

KA= 480/3/60

MA= 600/3/60
E= Electric

X= No Reheat
S= Steam Canister

X= No Humidifier
D= Downflow

U= Upflow
(Front Return)
AFX (Not Current)
AFX-XX-XXX-X
ModelCapacity KWConfigurationVoltageAir Pattern
AFX20 (6T)

27 (8T)

34 (10T)

41 (12T)

48 (14T)

62 (18T)

70 (20T)

90 (26T)

98 (28T)
A= Air Cooled

W= Water Cooled

G= Glycol Cooled
BA=208-230/3/60

KA= 480/3/60

MA= 600/3/60
D= Downflow

U= Upflow
(Front Return)

R= Upflow
(Rear Return)











AFX (Not Current)
AFX-XXX-X-XX
Model# of BaysCapacity TonConfigurationVoltageAir Pattern
AFX1 =1 Bay

2 =2 Bay

3 =3 Bay
06 (1 Bay)

08 (1 Bay)

10 (2 Bay)

12 (2 Bay)

14 (2 Bay)

18 (2 Bay)

20 (3 Bay)

26 (3 Bay)

28 (3 Bay)
A= Air Cooled

W= Water Cooled

G= Glycol Cooled
2=208-230/3/60

4= 480/3/60

6= 600/3/60
DF= Downflow

UD= Upflow
(Front or Rear Return)




CM (Not Current)
CM-XXX-X-XX-X
ModelCapacity KWConfigurationVoltageAir Pattern
CM003 (1T)

005 (1.5T)

007 (2T)

010 (3T)

014 (4T)

017 (5T)
A= Air Cooled

E= Air Cooled w/Multicool

R= Air Cooled w/Remote Condensing

W= Water Cooled

F= Water Cooled w/Multicool

G= Glycol Cooled

B= Glycol Cooled w/Multicool

P= Glycol Cooled w/Economizer

C= Chilled Water
BC=208-230/1/60

BA=208-230/3/60

FC=277/1/60

KA= 480/3/60
1-5T Air Cooled or
Self-Contained

1-3T Spot or Ducted

4-5T Ducted Only


S= Spot Cooled

D= Ducted
CM (Not Current)
CM-XX.X-X-XX-X-XX
ModelCapacity TonConfigurationVoltageAir PatternConfiguration
CM01.0

01.5

02.0

03.0

04.0

05.0
A= Air Cooled

W= Water Cooled

G= Glycol Cooled

R= Remote Condensing

C= Chilled Water

P= Precool
BC=208-230/1/60

BA=208-230/3/60

FC=277/1/60

KA= 480/3/60
S= Spot Cooled

D= Ducted
SC= Air Cooled Self-Contained

IR= Air Cooled Indoor Condenser

IG= Air Cooled Indoor Condensing

OR= Air Cooled Outdoor Condenser

OG= Air Cooled Remote Indoor Condensing




CM (Not Current) (MBH is equal to 1000 BTU)
CMXX-XXX-XXXX
ModelCapacity MBHConfigurationVoltageConfigurationCompressor
Info
Air PatternConfiguration
CM15 (1T)

20 (1.5T)

25 (2T)

40 (3T)

50 (4T)

65 (5T)
A= Air Cooled

W= Water Cooled

G= Glycol Cooled

C= Chilled Water

E= Fan Coil/Evap
BC=208/1/60

DC=230/1/60

BA=208/3/60

FC=277/1/60

DA= 230/3/60
C= Closed Coupled

R= Remote
X= No Compressor

2= With Compressor
S= Spot Cooled

D= Ducted
E= ECWS

P= Precool
CM Condenser/Condensing Unit (Not Current) (MBH is equal to 1000 BTU)
CNXX-XXX-XXXX
ModelCapacity MBHConfigurationVoltageConfigurationConfigurationControl
CR= Condenser

CN= Condensing Unit

GD= Drycooler
15 (1T)

20 (1.5T)

25 (2T)

40 (3T)

50 (4T)

65 (5T)
A= Air Cooled

W= Water Cooled

G= Glycol Cooled
DC=230/1/60

KC= 460/1/60
(FSC Only)

DA= 230/3/60

KA= 460/3/60
C= Closed Coupled

R= Remote
X= N/A

OP= Outdoor Propeller

IC= Indoor Centrifugal
C= Fan Cycle

F= Fan Speed

L= Flooded Control

X= N/A
CM Condenser/Condensing Unit/Drycooler (Not Current)
CM-XXX-XX.X-XXX-XX
ModelControlsCapacity TonAmbient TemperatureVoltage
CMAFL= Air Cooled Flooded

AFS= Air Cooled Fan Speed Control

GSS= Glycol Single Set Point

GDS= Glycol Dual Set Point
01.0

01.5

02.0

03.0

04.0

05.0
095= 95F

105= 105F

115= 115F
DC=230/1/60

KC= 460/1/60
(FSC Only)

DA= 230/3/60

KA= 460/3/60

CCT (Current)
CW100M-CXX-XXX
ModelCapacity KWModuleConfigurationVoltageReheatHumidifierAir Pattern
CW100 (28T)
M= Main
C= Chilled WaterBA=208-230/3/60

KA= 480/3/60

MA= 600/3/60
E= Electric

X= No Reheat
S= Steam Canister

X=No Humidifier
D=Downflow

U=Upflow
(Front Return)
CCT (Not Current)
CWXXX-CXX-X
ModelCapacity KWConfigurationVoltageAir Pattern
CW020 (6T)

027 (8T)

041 (12T)

050 (15T)

070 (20T)

087 (25T)

105 (30T)

123 (35T)

140 (40T)

175 (50T)

210 (60T)
C= Chilled WaterBA=208-230/3/60

KA= 480/3/60

MA= 600/3/60
D=Downflow

U=Upflow
(Front Return)

R= Upflow
(Rear Return)

CCT (Not Current)
CW-XX.X-C-XX-X
ModelCapacity TonConfigurationVoltageAir Pattern
CW12.0

15.0

20.0

25.0

30.0

35.0

40.0

50.0

60.0
C= Chilled WaterBA=208-230/3/60

KA= 480/3/60

MA= 600/3/60
D=Downflow

U=Upflow
(Front Return)

CCT (Not Current)
CCT-XX-XX
ModelCapacity TonConfigurationVoltage
CCT
12

15

20

25

30

35

40

50

60
C= Chilled Water2= 208, 220 or 230

4= 380, 415 or 460

6= 575














(DATAC) DTXX-CXX-XXX
Part Number or the CCT to the LEFTCapacity
Ton
ConfigurationVoltagePhase/FrequencyNot
Used
Not
Used
Air Pattern
DT12

15

20

25

30

35

40

50

60
C= Chilled WaterB= 208

C= 220

K= 460

M= 575

H= 415

D= 230

G= 380
A= 3/60

B= 3/50
XXU= Upflow

D= Downflow







































CCT (Not Current)
CCT( Capacity)-X(Voltage)X
ModelCapacity TonConfigurationVoltageConfiguration
CCTUnkownC= Chilled Water

A= Air Cooled

G= Glycol Cooled

W= Water Cooled

RC= Remote Condensing

ECWS= External Chilled Water Plus DX

CU= Mainframe Chiller System (4-30 ton in Air, Water, Glycol, PreFree Cool, and ECWS)

PC= PreFree Cool
2= 208, 220 or 230

4= 380, 415 or 460

6= 575
SC= Self-Contained







CCT (Not Current)
DX-XX.X-X-XX-X
ModelCapacity TonConfigurationVoltageAir Pattern
DX= Direct Expansion
06.0

08.0

10.0

15.0

20.0

24.0

30.0
A= Air Cooled

W= Water Cooled

G= Glycol Cooled

R= Remote Condensing

P= Precool
BC=208-230/1/60

BA=208-230/3/60

KA= 480/3/60

MA= 600/3/60
D= Downflow

U= Upflow


SH (Not Current)
SH-X(X)
ModelVoltageConfiguration
SH= Sky-Hook
(Ceiling Mount Unit)
Capacity 1 ¾ Ton
2= 208-230/1/60

3= 277/1/60
A= Air Cooled

W= Water Cooled

G= Glycol Cooled

C= Chilled Water
DH (Not Current)
DH-X(X)
ModelVoltageConfiguration
DH= Datahook
(Ceiling Mount Unit)
Capacity 2 ¾ Ton
2= 208-230/1/60

3= 277/1/60
A= Air Cooled

W= Water Cooled

G= Glycol Cooled

TC (Not Current)
TC-XX.X-X-XX-X
ModelCapacity TonConfigurationVoltageAir Pattern
TC= TechCool
02.0(Not in C)

03.0 (Not in C)

05.0 (Not in C)

08.0 (All Config.)

10.0 (All Config.)

04.0 (C Only)

06.0 (C Only)

12.0 (C Only)
A= Air Cooled

W= Water Cooled

G= Glycol Cooled

R= Remote Condensing

P= Precool

C= Chilled Water
BA=208-230/3/60

KA= 460/3/60

MA= 6575/3/60
D= Downflow

U= Upflow


TC (Not Current)
TC-XX.X-X-XX-X
ModelCapacity TonConfigurationVoltageAir PatternSpecial
Features
TC= TechCool
2 (Not in C)

3 (Not in C)

5 (Not in C)

8 (All Config.)

10 (All Config.)

4 (C Only)

6 (C Only)

12 (C Only)
A= Air Cooled

W= Water Cooled

G= Glycol Cooled

C= Chilled Water

E= Remote Condensing
2= 208, 220 or 230

4= 380, 415 or 460

6= 575
D=Downflow

UD=Upflow
PC= Precool (Only in 2, 3, & 5 Ton)

ECWS= External Chilled Water Supply
(TC Part Number) TCX-XXX-XXX
Part Number or the TC to the LEFTCapacity
Ton
ConfigurationVoltagePhase/FrequencySpecial
Features
Compressor
Info
Air Pattern
TC2

3

4

5

6

8

10

12
A= Air Cooled

W= Water Cooled

G= Glycol Cooled

C= Chilled Water

E= Remote Condensing
B= 208

C= 220

K= 460

M= 575

H= 415

D= 230

G= 380
A= 3/60

B= 3/50
X= none