Video: How to setup an ATV630 Process drive to follow AI2 instead of AI1 as reference?
Issue:
Wants to setup an ATV630 Process drive to follow AI2 (Analog Input 2), instead of AI1 as reference.

Product Line:
ATV630, Altivar Process

Resolution:



From the Main Menu:
  1. Scroll down and select menu 5 Complete Settings
  2. Scroll down and select menu 5.5 Command and Reference
  3. Select Ref Freq 1 Config and assign it to AI2
  4. Unless an HOA (Hand Off Auto) function is used, set Ref 1B switching to [Ref Freq channel 1]
  5. Also set Freq Switch Assign to [Ref Freq Channel 1].

Schneider Electric Hong Kong

Explore more
Range:
Users group

Discuss this topic with experts

Visit our Community for first-hand insights from experts and peers on this topic and more.
Explore more
Range:

Need help?

  • Product Selector

    Quickly and easily find the right products and accessories for your applications.

  • Get a Quote

    Start your sales enquiry online and an expert will connect with you.

  • Where to buy?

    Easily find the nearest Schneider Electric distributor in your location.

  • Help Centre

    Find support resources for all your needs, in one place.

  • Products Documentation
  • Software Downloads
  • Product Selector
  • Product Substitution and Replacement
  • Help and Contact centre
  • Find our Offices
  • Get a Quote
  • Where to buy
  • Careers
  • Company Profile
  • Report a misconduct
  • Accessibility
  • Newsroom
  • Investors
  • EcoStruxure
  • Job Search
  • Blog
  • Privacy Policy
  • Cookie Notice
  • Terms of use
  • Change your cookie settings