Issue:
Are there impedance on the analog inputs of the ATV600 / 900 series drives?
Product Line:
ATV600 and ATV900
Environment:
All models, all serial numbers
Cause:
Customer's analog signal may have insufficient power to properly drive the input.
Resolution:
If the analog input is configured for voltage, then the impedance is 30K Ohms.
If the analog input is configured for current, then the impedance is 250 Ohm. This is done so that you do not need to break the circuit, and place a milliamp meter in series to measure the input signal. You can measure DC volts across this resistor (analog input to ground) to determine the input current. 4ma will product 1.0VDC, 20ma will product 5.0VDC.
Are there impedance on the analog inputs of the ATV600 / 900 series drives?
Product Line:
ATV600 and ATV900
Environment:
All models, all serial numbers
Cause:
Customer's analog signal may have insufficient power to properly drive the input.
Resolution:
If the analog input is configured for voltage, then the impedance is 30K Ohms.
If the analog input is configured for current, then the impedance is 250 Ohm. This is done so that you do not need to break the circuit, and place a milliamp meter in series to measure the input signal. You can measure DC volts across this resistor (analog input to ground) to determine the input current. 4ma will product 1.0VDC, 20ma will product 5.0VDC.
Released for: Schneider Electric Hong Kong




Need help?
Product Selector
Quickly and easily find the right products and accessories for your applications.
Get a Quote
Start your sales enquiry online and an expert will connect with you.
Where to buy?
Easily find the nearest Schneider Electric distributor in your location.
Help Centre
Find support resources for all your needs, in one place.