{}

Our Brands

Impact-Company-Logo-English Black-01-177x54

Welcome to the Schneider Electric Website

Welcome to our website.
Search FAQs
Why I am unable to set the date and time of IMU with Compact NSX/CompactNS/Masterpact NT/NW?
If you are unable to set date and time of IMU with Compact NSX/CompactNS/Masterpact NT/NW then please check the firmware version of the BCM ULP through Ecoreach Firmware Upgrade. If the firmware version of BCM ULP is 3.0.4 consider changing the firmware version of the BCM ULP to firmware version 3.0.7.

Schneider Electric Hong Kong

Explore more
Range:
Articles that might be helpful Users group

Discuss this topic with experts

Visit our Community for first-hand insights from experts and peers on this topic and more.
Explore more
Range: