Our Brands

Impact-Company-Logo-English Black-01-177x54

Welcome to the Schneider Electric Website

Welcome to our website.
		
How can we help you today?
How to control (run stop, freq reference) Altivar ATV12 via remote terminal VW3A1006, VW3A1007
From factory setting you need to enter conf menu and set FR1=LCC
Then run and stop buttons on remote terminal will work, but display by default will not show frequency reference. Instead motor speed is displayed.
To change freq setpoint on remote terminal, it is necessary to enter rfr menu and select frh. Then freq reference will remain on HMI. Simultaneously, RFR LED diode on HMI will be lit. If the led diode is not lit, rfr menu is not active (and motor speed is shown on HMI).

Schneider Electric Hong Kong

Explore more
Range:
Users group

Discuss this topic with experts

Visit our Community for first-hand insights from experts and peers on this topic and more.
Explore more
Range:

Need help?

  • Product Selector

    Quickly and easily find the right products and accessories for your applications.

  • Get a Quote

    Start your sales enquiry online and an expert will connect with you.

  • Where to buy?

    Easily find the nearest Schneider Electric distributor in your location.

  • Help Centre

    Find support resources for all your needs, in one place.

  • Products Documentation
  • Software Downloads
  • Product Selector
  • Product Substitution and Replacement
  • Help and Contact centre
  • Find our Offices
  • Get a Quote
  • Where to buy
  • Careers
  • Company Profile
  • Report a misconduct
  • Accessibility
  • Newsroom
  • Investors
  • EcoStruxure
  • Job Search
  • Blog
  • Privacy Policy
  • Cookie Notice
  • Terms of use
  • Change your cookie settings