Ports used by each component of PowerChute Business Edition.
Published date:
27 January 2021
Issue:
What ports are used by each component of PowerChute Business Edition
Product Line:
PowerChute Business Edition
Environment:
All supported OS
Cause:
Informational
Solution:
TCP
2161 – Communication between Server and Agent (PowerChute 9.2.1 and below)
2160 – Communication between Console and Server (PowerChute 6.x)
2260 – Communication between Console and Server (PowerChute 7.x, 8.x, 9.x ending at 9.2.1)
3052 – Agent Web UI and Logging features (PowerChute 9.2.1 and below)
6547 – Agent Web UI (PowerChute 9.x and 10.x)
UDP
2161 – Discovery of Agents by Server (PowerChute 9.2.1 and below)
2160 – Discovery of Servers by Console (PowerChute 9.2.1 and below)
7846 – Business Edition SNMP Agent