{}

Our Brands

Impact-Company-Logo-English Black-01-177x54

Welcome to the Schneider Electric Website

Welcome to our website.
Search FAQs
ENM 8.3 SEEG.exe error while trying to refresh tags, dll file has already loaded from a different location
Issue
After applying a patch to ENM, user cannot refresh tags. The error message suggests a service is not running however all services are running. In the ENM event log the following message is included
"API restriction: The assembly 'file:///C:\Program Files (x86)\Schneider Electric\StruxureWare Solutions\Event Gathering Service\[some file name].dll' has already loaded from a different location. It cannot be loaded from a new location within the same appdomain.

Product
ENM 8.3

Environment
Applying patch to update dll file

Resolution
The likely cause is because the updated dll and original dll (with a different name) are in the same folder. Move the old dll file to a new location and restart the Event Gathering Service.

Schneider Electric Indonesia

Explore more
Range:
Articles that might be helpful Users group

Discuss this topic with experts

Visit our Community for first-hand insights from experts and peers on this topic and more.
Explore more
Range: