Example on configuring an NOR to get a timestamp with a DNP3 point
Issue
Provide an example on how to configure a DNP3 point in the BMXNOR0200 to get a timestamp when the point
DNP3 value changes.

Product Line
BMXNOR0200

Environment
Windows 10

Resolution
The following steps can be used to configure the BMXNOR0200 for accessing a DNP3 point with a timestamp
from a SCADA.
  • Click on 'Data Mapping' in the 'Setup' menu list to open the 'Data Mapping' web page.
dF

  • Click on the down arrow next to the textbox labeled 'Select a type id'
ATQRWH

  • Select the DNP3 point type from the drop down list.
RQET
  • Click on Add
ERQT

  • Enter the appropriate information to define the DNP3 point.
  • Select 'CPU Reg Mapping' as 'Value only'.
  • Select 'Default Static Variation' as 'g1v1 Binary In'.
  • Select 'Default Event Variation' as 'g2v2 Binary Input with time'.
  • Click on 'Change'.
RET

  • Click on 'Events' in the 'Setup' menu list.
  • Click on the down arrow next to the textbox labeled 'Select a type id'
ERT

  • Select the event type from the drop down list.
  • Click on 'Add'.
ERT

  • Click on the down arrow next to 'Event Store Mode' and select the appropriate store mode.
  • Click on the down arrow next to 'Buffer String' and select the appropriate buffer string type..
  • Enter the CPU register address that will be used to store the events count.
  • Click on 'Add'.
3T

  • Click on 'Reset Communications' to allow the changes to take effect..
RT

Schneider Electric Indonesia

Example on configuring an NOR to get a timestamp with a DNP3 point
Issue
Provide an example on how to configure a DNP3 point in the BMXNOR0200 to get a timestamp when the point
DNP3 value changes.

Product Line
BMXNOR0200

Environment
Windows 10

Resolution
The following steps can be used to configure the BMXNOR0200 for accessing a DNP3 point with a timestamp
from a SCADA.
 
  • Click on 'Data Mapping' in the 'Setup' menu list to open the 'Data Mapping' web page.
dF

 
  • Click on the down arrow next to the textbox labeled 'Select a type id'
ATQRWH

 
  • Select the DNP3 point type from the drop down list.
RQET
 
  • Click on Add
ERQT

 
  • Enter the appropriate information to define the DNP3 point.
  • Select 'CPU Reg Mapping' as 'Value only'.
  • Select 'Default Static Variation' as 'g1v1 Binary In'.
  • Select 'Default Event Variation' as 'g2v2 Binary Input with time'.
  • Click on 'Change'.
RET

 
  • Click on 'Events' in the 'Setup' menu list.
  • Click on the down arrow next to the textbox labeled 'Select a type id'
ERT

 
  • Select the event type from the drop down list.
  • Click on 'Add'.
ERT

 
  • Click on the down arrow next to 'Event Store Mode' and select the appropriate store mode.
  • Click on the down arrow next to 'Buffer String' and select the appropriate buffer string type..
  • Enter the CPU register address that will be used to store the events count.
  • Click on 'Add'.
3T

 
  • Click on 'Reset Communications' to allow the changes to take effect..
RT
 

Schneider Electric Indonesia

Explore more
Product:
Range:
Explore more
Product:
Range:
Users group

Discuss this topic with experts

Visit our Community for first-hand insights from experts and peers on this topic and more.
Users group

Discuss this topic with experts

Visit our Community for first-hand insights from experts and peers on this topic and more.
Explore more
Product:
Range:
Explore more
Product:
Range:
move-arrow-top
Your browser is out of date and has known security issues.

It also may not display all features of this website or other websites.

Please upgrade your browser to access all of the features of this website.

Latest version for Google Chrome, Mozilla Firefox or Microsoft Edgeis recommended for optimal functionality.
Your browser is out of date and has known security issues.

It also may not display all features of this website or other websites.

Please upgrade your browser to access all of the features of this website.

Latest version for Google Chrome, Mozilla Firefox or Microsoft Edgeis recommended for optimal functionality.