{}

Our Brands

Impact-Company-Logo-English Black-01-177x54

Welcome to the Schneider Electric Website

Welcome to our website.
Search FAQs
What would cause the A1U1 parameter not to show up in the Fr1 menu on the ATV320 drive?
Issue:
A1U1 parameter does not show up in the Fr1 menu on the ATV320 drive.

Product Line:
Altivar ATV320

Environment:
All

Cause:
Wants to setup the knob as the speed control

Resolution:
A1U1 will only show up in the Fr1 menu when you assign CHCF to SEP (Profile= Separate). Changing the value of this parameter requires holding the enter button for 2 seconds.

Schneider Electric Indonesia

Attachment(s)
ATV320_programming_manual_EN_NVE41295_01.pdf [2.05 MB]
Explore more
Range:
Articles that might be helpful Users group

Discuss this topic with experts

Visit our Community for first-hand insights from experts and peers on this topic and more.
Explore more
Range: