{}

Our Brands

Impact-Company-Logo-English Black-01-177x54

Welcome to the Schneider Electric Website

Welcome to our website.
Search FAQs
What does an EEF1 fault on an Altivar Process Drive mean?

Article available in these languages: Spanish

Issue:
Troubleshoot for an EEF1 fault on a Process Drive

Product Line:
Altivar 6xx and 9xx Process Drives

Environment:
All

Cause:
An error of the internal memory of the control block has been detected.

Resolution:
Verify the environment (electromagnetic compatibility).
This detected error requires a power reset. Remove line voltage until the display goes all the way out. Then reapply line voltage.
If cycling line voltage doesn't clear the fault, save your programming in the keypad or SoMove, and perform a factory reset.
After factory reset cycle line voltage again.
If the fault remains, drive replacement is required.

Schneider Electric Indonesia

Explore more
Range:
Articles that might be helpful Users group

Discuss this topic with experts

Visit our Community for first-hand insights from experts and peers on this topic and more.
Explore more
Range: