How can we help you today?

MSDS/SDS & Electrolyte Data for APC SYBTU1‑PLP, SYBTU2‑PLP, GVSBTU, GVSBTHU Series Batteries

Issue

Where to find electrolyte volume and safety data for APC modular batteries:

  • SYBTU1-PLP
  • SYBTU2-PLP
  • SE Modular Batteries: GVSBTU, GVSBTHU, GVSBTHULL

Product Line

  • SYBTU1-PLP / SYBTU2-PLP
  • GVSBTU / GVSBTHU / GVSBTHULL

Environment

  • Symmetra PX (PX1, PX2, 250–500 kVA)
  • SUVT
  • Galaxy 3500
  • Galaxy VS
  • EZUPS

Information

  • Electrolyte Volume: Refer to Application Note 143 for detailed values.
    • SYBTU1-PLP: Used in PX1 (20–96 kVA), SUVT, Galaxy 3500
    • SYBTU2-PLP: Used in PX2 (100 kVA) and PX 250/500 kVA
  • Safety Data Sheets (SDS): Attached for reference.
  • Application Note 143: Attached for reference.


Galaxy VS Modular Batteries:

Battery TypeElectrolyte WeightElectrolyte Volume
(kg)(lbs)(ml)(gal)
GP1272F2FR0.51.113780.1
HR1234WF2FR0.440.983330.09
UP-PW1245P10.47941.0573780.0998
Battery TypeElectrolyte WeightElectrolyte Volume
(kg)(lbs)(ml)(gal)
GVSBTU511.137801
GVSBTHU4.49.833300.9
GVSBTHULL4.79410.5737800.998
Battery TypeElectrolyte WeightElectrolyte Volume
(kg)(lbs)(ml)(gal)
GVSBT42044.4151204
GVSBTH417.639.2133203.6
GVSBTH4LL19.17642.28151203.992

Schneider Electric Indonesia

Discuss this topic with experts

Visit our Community for first-hand insights from experts and peers on this topic and more.

Need help?

Product Selector

Quickly and easily find the right products and accessories for your applications.

Get a Quote

Start your sales enquiry online and an expert will connect with you.

Where to buy?

Easily find the nearest Schneider Electric distributor in your location.

Help Centre

Find support resources for all your needs, in one place.