Which phase current is used for the ANSI 49 (Thermal Overload) thermal replica calculation?
Issue
The thermal overload function is tripping, and the customer wants to verify which current value is used in the thermal model.
Product
MiCOM Series Protection relays
Environment
MiCOM protection relays
ANSI 49 Thermal Overload protection
Current measurement and thermal replica calculation
Cause
Clarification is required regarding how the relay determines the input current for the thermal overload function, especially during unbalanced load or fault conditions.
Resolution
The MiCOM relay family automatically uses the largest phase current among the three phases for the ANSI 49 thermal replica calculation. This ensures worst‑case heating is always considered in the thermal model.
Released for: Schneider Electric Ireland










Need help?
Product Selector
Quickly and easily find the right products and accessories for your applications.
Where to buy?
Easily find the nearest Schneider Electric distributor in your location.
Help Centre
Search topic-related frequently asked questions to find answers you need.