Issue:
Problems may arise trying to connect using an optical probe to PowerLogic and ION Meters
Product Line:
PowerLogic and ION meters
Environment:
Optical port communications
Cause:
The serial settings for the connection are configured incorrectly, most notably in the timing settings of the probe. 
Resolution:
Software Settings Used to Communicate with Optical Probes
 Summary- The following compatibility table provides communications settings for use with Optical Probe models and various Power Measurement software. - Probe PEGASYS NTMeter ShopPEGASYS 9xION EnterpriseION SetupION Reader- Comments - MicroTel PMC-250 YesYesYesYesYesYes- external power via mouse plug - MicroTel PMC-500 NoYes1Yes1Yes1Yes1Yes1- external power via mouse plug - uDataNet PMC-250-300 YesYesYesYesYesYes- external power via mouse plug - uDataNet PMC-500-300 NoYes1Yes1Yes1Yes1Yes1- external power via mouse plug, DTR switch selectable - uDataNet PMC-500-301 Yes2Yes3Yes3Yes3Yes3Yes3- external power via mouse plug - GE SmartCoupler SC-1 NoYes1Yes1Yes1Yes1Yes1- Battery pack uses standard 9V battery - ABB Unicom III NoNoNoNoYes4Yes4- Self Powered -  - 1 - Requires DTR to be forced off via software settings. 2 - Requires DTR switch on probe to be set to the open position. 3 - Requires either DTR to be forced off via software settings or DTR switch on probe to be set to the open position. 4 - Requires both DTR to be forced off and RTS to be forced on (or vice versa) via software settings. 
 
- 1 - Requires DTR to be forced off via software settings. 
 
-  
Released for: Schneider Electric Ireland