Where is the 0-10vdc analog input speed reference wired on the ATV71 / ATV61 drives?
Issue:
ATV61/ATV71 speed reference wired installation with 0-10Vdc analog input.
Product Line:
ATV71 ATV61
Environment:
All
Cause:
Wiring 0-10vdc input
Resolution:
Typically, 0-10vdc analog input reference is connected between AI1 (+) and com.
Please note there is a jumper between AI1- and com. Leave this jumper in place. If the jumper were removed, AI1 would become a bipolar (-10 to +10V) input.
Programming:
Menu 1.5, AI1 configuration, choose 0 min and 10vdc max.
AI2 can also be configured for a voltage reference in the I/O menu (1.5). Under AI2 configuration, select assignment " voltage type" , minimum and maximum values 0 to 10vdc..
ATV61/ATV71 speed reference wired installation with 0-10Vdc analog input.
Product Line:
ATV71 ATV61
Environment:
All
Cause:
Wiring 0-10vdc input
Resolution:
Typically, 0-10vdc analog input reference is connected between AI1 (+) and com.
Please note there is a jumper between AI1- and com. Leave this jumper in place. If the jumper were removed, AI1 would become a bipolar (-10 to +10V) input.
Programming:
Menu 1.5, AI1 configuration, choose 0 min and 10vdc max.
AI2 can also be configured for a voltage reference in the I/O menu (1.5). Under AI2 configuration, select assignment " voltage type" , minimum and maximum values 0 to 10vdc..
Released for: Schneider Electric Ireland
Explore more
Range:
Explore more
Range:
Need help?
Product Selector
Quickly and easily find the right products and accessories for your applications.
Where to buy?
Easily find the nearest Schneider Electric distributor in your location.
Help Centre
Search topic-related frequently asked questions to find answers you need.