Our Brands

Impact-Company-Logo-English Black-01-177x54

Welcome to the Schneider Electric Website

Welcome to our website.
		
How can we help you today?
What is the error in % on class 0.5s and class 1?
For Current transformers the tolerance for each class is as follows:

For class 0.5s, if:
I < 0.01 x In - Percentage ratio error 1.5%
0.01 x In < I < 0.05 x In - Percentage ratio error 0.75%
0.05 x In < I < 0.20 x In - Percentage ratio error 0.5%
0.20 x In < I < 1.00 x In - Percentage ratio error 0.5%
1.00 x In < I < 1.20 x In - Percentage ratio error 0.5%

For class 1, if:
I < 0.05 x In - Percentage ratio error 3%
0.05 x In < I < 0.20 x In - Percentage ratio error 1.5%
0.20 x In < I < 1.00 x In - Percentage ratio error 1.0%
1.00 x In < I < 1.20 x In - Percentage ratio error 1.0%

For more information please refer to the standards IEC 61869-2 (2102)

Schneider Electric Ireland

Users group

Discuss this topic with experts

Visit our community and get advice from experts and peers on this topic and more
  • Products Documentation
  • Software Downloads
  • Product Selector
  • Product Substitution and Replacement
  • Help and Contact Centre
  • Find our Offices
  • Where to buy
  • Schneider Electric Community
  • Careers
  • Company Profile
  • Report a misconduct
  • Accessibility
  • Newsroom
  • Investors
  • EcoStruxure
  • Job Search
  • Blog
  • Privacy Policy
  • Cookie Notice
  • Terms of use
  • Change your cookie settings