How to program the ATV212 drive to follow the ACC and DEC set times?

Issue:
Program ATV212 to follow the ACC and DEC set times.

Product Line:
Altivar 212

Environment:
ACC/DEC times

Cause:
N/A

Resolution:
Go into AUF (hit mode).
Arrow down to AU1 and change value from 1 to 0.
Set the ACC and DEC to the desired ramp up and ramp down times.