Yes it is possible, you will need a low voltage OF (29452) connected to a smartlink modbus (A9XMSB11).
See below example of connection:
Link to user guide, see page 52.
https://www.se.com/uk/en/download/document/DOCA0123EN/
You can also use the IFM and BSCM to monitor the status over Modbus.