{}

Our Brands

Impact-Company-Logo-English Black-01-177x54

Welcome to the Schneider Electric Website

Welcome to our website.
Search FAQs
Is it possible to monitor the status of NSX switch over modbus?
Yes it is possible, you will need a low voltage OF (29452) connected to a smartlink modbus (A9XMSB11).
See below example of connection:
Connection guide
Link to user guide, see page 46.
https://www.se.com/uk/en/download/document/DOCA0123EN/

Schneider Electric Ireland

Explore more
Product:
Users group

Discuss this topic with experts

Visit our Community for first-hand insights from experts and peers on this topic and more.
Explore more
Product: