Does the NSX range of circuit breakers offer Generator protection?

Please see the chart below and the online catalogue. In the catalogue, please refer to page B-53.

The Micrologic 2 G trip units are used for the protection of systems supplied by generators and offer better suited low pick-up solutions.  They can be mounted on all Compact NSX100/160/250 circuit breakers.  Circuit breakers equipped with Micrologic G trip units protect systems supplied by generators (lower short-circuit currents than with transformers) and distribution systems with long cable lengths (fault currents limited by the impedance of the cable).