How can we help you today?

How to time synchronize Scadapack RTU from Clear Scada over DNP3 ?

Scadapack RTU can be time synchronized with Clear Scada over DNP3 either over serial or LAN.  Refer attached technical note for implementation.

Schneider Electric Ireland

Discuss this topic with experts

Visit our community and get advice from experts and peers on this topic and more

Explore more

Need help?

Product Selector

Quickly and easily find the right products and accessories for your applications.

Where to buy?

Easily find the nearest Schneider Electric distributor in your location.

Help Centre

Search topic-related frequently asked questions to find answers you need.