What’s the definition of each bit of Setpoint Status Validity (Modbus Registers 2420-2421) in PM8240?

Issue
What is the definition of each bit of Setpoint Status Validity (Modbus Registers 2420-2421) in a PM8240?

Product Line
PM8000 Series

Environment
PM8000 Register List

Resolution
Register 2420

This register indicates which bits are currently active, or which bit-mapped inputs are marked as NA.

Bit 0 = Over I a - Validity (Status (Enabled or Disabled))
Bit 1 = Over I b - Validity (Status (Enabled or Disabled))
Bit 2 = Over I c - Validity (Status (Enabled or Disabled))
Bit 3 = Over I 4 - Validity (Status (Enabled or Disabled))
Bit 4 = Over V unbal - Validity (Status (Enabled or Disabled))
Bit 5 = Over kW sd - Validity (Status (Enabled or Disabled))
Bit 6 - Not Implemented
Bit 7 - Not implemented
Bit 8 - Not Implemented
Bit 9 - Not implemented
Bit 10 - Not Implemented
Bit 11 - Not implemented
Bit 12 - Not Implemented
Bit 13 - Not implemented
Bit 14 - Not Implemented
Bit 15 - Not implemented

Register 2421

This register indicates the current state of the selected input (either True or False).

Bit 0 = Over I a - Current State (True or False)
Bit 1 = Over I b - Current State (True or False)
Bit 2 = Over I c - Current State (True or False)
Bit 3 = Over I 4 - Current State (True or False)
Bit 4 = Over V unbal - Current State (True or False)
Bit 5 = Over kW sd - Current State (True or False)
Bit 6 - Not Implemented
Bit 7 - Not implemented
Bit 8 - Not Implemented
Bit 9 - Not implemented
Bit 10 - Not Implemented
Bit 11 - Not implemented
Bit 12 - Not Implemented
Bit 13 - Not implemented
Bit 14 - Not Implemented
Bit 15 - Not implemented


The following examples show the status and state of the Setpoint Modules for the related parameters using Data Mapping I/O Module.

Over I a
Over I b
Over I c
Over I 4
Over V unbal
Over kW sd

When all Setpoint Modules, including ‘Over I b,’ are disabled:

Setpoint Status and State-Disabled and Inactive

When only Setpoint Module 'Over Ib' is enabled with true state:

Setpoint Status and State-Enabled and true

In the first image, registers 2420 and 2421 display 0 for all bits, including Bit 1. Accordingly, the input registers, including Over I b, are marked as NA because the corresponding Setpoint Module was disabled.

In the second image, registers 2420 and 2421 display 1 only for Bit 1. This is because the setup register of the Setpoint Module 'Over I b' was changed to Enabled, and its output register indicates True, meaning the related alarm is active.

Schneider Electric Ireland

Explore more
Range:
Users group

Discuss this topic with experts

Visit our community and get advice from experts and peers on this topic and more
Explore more
Range:
  • Products Documentation
  • Software Downloads
  • Product Selector
  • Product Substitution and Replacement
  • Help and Contact Centre
  • Find our Offices
  • Where to buy
  • Schneider Electric Community
  • Careers
  • Company Profile
  • Report a misconduct
  • Accessibility
  • Newsroom
  • Investors
  • EcoStruxure
  • Job Search
  • Blog
  • Privacy Policy
  • Cookie Notice
  • Terms of use
  • Change your cookie settings