Does the ATV212 preset speed function override PID control?
Issue:
Overriding PID control with ATV212 preset speed function.
Product Line:
Altivar 212 ATV212
Environment:
All models
Cause:
Activation of preset speed needs to override PID control
Resolution:
The preset speed activation does not override PID control. When activating the logic input for a preset speed, also activate a separate logic input that is assigned to 14 (PID disable) to deactivate PID control. This way, the preset takes control.