How can it be verified the motor is running through the shorting contactor and not the ATS48?
Issue:
Validate motor is running through the shorting contactor, not the soft starter.
Product Line:
ATS48
Environment:
All serial numbers
Cause:
Testing the contactor
Resolution:
Verify the r2A and r2C is closed.
Measure motor current on the load side of the shorting contactor.
Validate motor is running through the shorting contactor, not the soft starter.
Product Line:
ATS48
Environment:
All serial numbers
Cause:
Testing the contactor
Resolution:
Verify the r2A and r2C is closed.
Measure motor current on the load side of the shorting contactor.