How can we help you today?

Can the ION meter template file be read before sending it to the meter?

Issue
A user wants to view an ION template file before sending it to the meter

Product Line
Powerlogic ION meters

Environment
ION Setup
Text Editor

Resolution

The meter template file (DCF) is not human-readable and therefore cannot be read before sending it to the meter. When opened in a text editor like notepad, the file will display non standard characters.

Schneider Electric Ireland

Explore more

Discuss this topic with experts

Visit our community and get advice from experts and peers on this topic and more

Explore more

Need help?

Product Selector

Quickly and easily find the right products and accessories for your applications.

Where to buy?

Easily find the nearest Schneider Electric distributor in your location.

Help Centre

Search topic-related frequently asked questions to find answers you need.