What would cause an bOF or brake resistor overload fault on the ATV630 and ATV930 Process drives?
Issue:
ATV630 and ATV930 causes with an bOF or brake resistor overload fault.

Product Line:
ATV630 and ATV930 Process drives

Environment:
All

Cause:
Parameter setting of the braking resistor not correct (brtC, brV, brP)

Resolution:
Principle:
The thermal model of the braking resistor has detected and overload.The themal state of the BR can be monitored with the parameter tHb.

Probable cause:
- parameter setting of the braking resistor not correct (brtC, brV, brP)

Remedies:
- check the nominal power of the braking resistor.
- verify the BR parameters brP, brV, brtC
- check with SoMove service section the thermal states TH1R / TH2R / TH3R
- check the thermal state parameter tHb [Braking Resistor monitoring]

Schneider Electric Ireland

Explore more
Range:
Users group

Discuss this topic with experts

Visit our community and get advice from experts and peers on this topic and more
Explore more
Range:

Need help?

  • Product Selector

    Quickly and easily find the right products and accessories for your applications.

  • Where to buy?

    Easily find the nearest Schneider Electric distributor in your location.

  • Help Centre

    Search topic-related frequently asked questions to find answers you need.

  • Products Documentation
  • Software Downloads
  • Product Selector
  • Product Substitution and Replacement
  • Help and Contact Centre
  • Find our Offices
  • Where to buy
  • Careers
  • Company Profile
  • Report a misconduct
  • Accessibility
  • Newsroom
  • Investors
  • EcoStruxure
  • Job Search
  • Blog
  • Privacy Policy
  • Cookie Notice
  • Terms of use
  • Change your cookie settings