How can we help you today?

How to know the absence of x80 IO in local M580 rack when it is configured as Device DDT ?

1.Issue

How to know the absence of x80 IO in local M580 rack when it is configured as Device DDT ?

2.Environment

M580 series ,X80

3.Resolution

The detail diagnostics status of x80 IO could be accessed by implementing READ_STS_MX.
Here are two samples to get status for digital and analog modules.


jpg 1

When COM_FLT is set to 1 ,it means the module could not be detected by CPU and module would be absent in the rack.

JPG 2

JPG 3

Schneider Electric Ireland

Attachment(s)

Explore more

Discuss this topic with experts

Visit our community and get advice from experts and peers on this topic and more

Explore more

Need help?

Product Selector

Quickly and easily find the right products and accessories for your applications.

Where to buy?

Easily find the nearest Schneider Electric distributor in your location.

Help Centre

Search topic-related frequently asked questions to find answers you need.