How can we help you today?
How to calculate “Tt Timing setting accuracy” of RM17TE00 product?
The RM17TE00 product’s Tt timing setting is +/-10% (full scale).
Example:
When the Tt setting is configured to 5s, the actual time delay is 5s +/-10% of the full-scale value.
Actual Time Delay, Tt = 5s +/- (10% x 10s) = 5s +/-1s
Example:
When the Tt setting is configured to 5s, the actual time delay is 5s +/-10% of the full-scale value.
Actual Time Delay, Tt = 5s +/- (10% x 10s) = 5s +/-1s