Our Brands

Impact-Company-Logo-English Black-01-177x54

Welcome to the Schneider Electric Website

Welcome to our website.
		
How can we help you today?
Sepam Series 80 information saving on power failure

The saving of information depends on whether or not the battery is present. In the event of a Sepam series 80 power failure, certain data will only be saved if the battery is present.

The data listed below are only saved if the battery is present:

  • Peak demand current
  • Peak demand active power
  • Peak demand reactive power
  • Tripping context
  • Tripping current
  • Disturbance recordings
  • Starting current
  • Starting time
  • Alarm message history
  • date and time
The data listed below are saved with or without a battery present:
  • Calculated active energy
  • Calculated reactive energy
  • Number of trips (phase overcurrent and earth fault)
  • Machine heat rise
  • Running hours counter and operating time
  • Cumulative breaking current
  • Number of operations
  • Operating time
  • Charging time
  • Number of rackouts
Important: All the data contained in the cartridge are saved.

Schneider Electric Ireland

Explore more
Range:
Users group

Discuss this topic with experts

Visit our community and get advice from experts and peers on this topic and more
Explore more
Range:

Need help?

  • Product Selector

    Quickly and easily find the right products and accessories for your applications.

  • Where to buy?

    Easily find the nearest Schneider Electric distributor in your location.

  • Help Centre

    Search topic-related frequently asked questions to find answers you need.

  • Products Documentation
  • Software Downloads
  • Product Selector
  • Product Substitution and Replacement
  • Help and Contact Centre
  • Find our Offices
  • Where to buy
  • Careers
  • Company Profile
  • Report a misconduct
  • Accessibility
  • Newsroom
  • Investors
  • EcoStruxure
  • Job Search
  • Blog
  • Privacy Policy
  • Cookie Notice
  • Terms of use
  • Change your cookie settings