Our Brands

Impact-Company-Logo-English Black-01-177x54

Welcome to the Schneider Electric Website

Welcome to our website.
		
How can we help you today?
How can an ATS46 or ATS48 be used with an undersized motor or no motor?
Issue:
ATS46 or ATS48 using an undersized motor or not using motor.

Product Line:
ATS46, ATS48

Environment:
All

Cause:
NA

Resolution:
A minimum load current is required for SCR conduction. Starter will trip on PHF (Phase Fault) if the motor current draw is less than 10% of the nominal motor current (adjustable down to 5% on ATS48).

A very small motor or motor loads that can not pull adequate current may require a smaller soft starter.
For testing purposes only, the SST parameter can be turned on under Level 3 parameters(drC menu on ATS48). This SST mode will automatically reset to "NO" when power is cycled.
SST will NOT allow the soft starter to operate with no motor.

Schneider Electric Ireland

Explore more
Range:
Users group

Discuss this topic with experts

Visit our community and get advice from experts and peers on this topic and more
Explore more
Range:

Need help?

  • Product Selector

    Quickly and easily find the right products and accessories for your applications.

  • Where to buy?

    Easily find the nearest Schneider Electric distributor in your location.

  • Help Centre

    Search topic-related frequently asked questions to find answers you need.

  • Products Documentation
  • Software Downloads
  • Product Selector
  • Product Substitution and Replacement
  • Help and Contact Centre
  • Find our Offices
  • Where to buy
  • Careers
  • Company Profile
  • Report a misconduct
  • Accessibility
  • Newsroom
  • Investors
  • EcoStruxure
  • Job Search
  • Blog
  • Privacy Policy
  • Cookie Notice
  • Terms of use
  • Change your cookie settings