The table below details the Torque requirements for the majority of the Acti9 product range:
The table below details the Torque requirements for the majority of the Acti9 product range:
| Range | Type | Tightening Torque |
| iC60H Circuit Breaker | 1 to 25 A | 2 Nm |
| iC60H Circuit Breaker | 32 to 63 A | 3.5 Nm |
| iC60H RCBO | N in and L in | 3.5 Nm |
| iC60H RCBO | L out and N out | 2 Nm |
| Vigi iC60 add-on RCD | 25 A | 2 Nm |
| Vigi iC60 add-on RCD | 40 to 63A | 3.5 Nm |
| iID RCCB | iID | 3.5 Nm |
| Electrical auxiliaries for iC60, iID, iDPN Vigi, RCA and ARA | Indication auxiliaries | 1 Nm |
| Electrical auxiliaries for iC60, iID, iDPN Vigi, RCA and ARA | Tripping auxiliaries | 1 Nm |
| Accessories for iC60, iID, iDPN Vigi, Reflex iC60, RCA, ARA, iSW | Multi-cable terminal | 2 Nm |
| Accessories for iC60, iID, iDPN Vigi, Reflex iC60, RCA, ARA, iSW | 50 mm² terminal Al | 10 Nm |
| Accessories for iC60, iID, iDPN Vigi, Reflex iC60, RCA, ARA, iSW | Screw-on connection for ring terminal | 2 Nm |
| iDPN circuit breakers | DT40, i DPN, C40 | 2 Nm |
| iDPN circuit breakers | DT60 | 3.5 Nm |
| iDPN Vigi RCD | 4 to 40 A | 2 Nm |
| iC120H circuit breakers | 63 to 125 A | 3.5 Nm |
| Vigi iC120 add-on RCD | Vigi C120 | 3.5 Nm |
| Accessories for iC120, DPN, DPN Vigi, C60H-DC, SW60-DC, C60NA-DC, C60PV-DC, iSW devices | Multi-cable terminal | 2 Nm |
| Accessories for iC120, DPN, DPN Vigi, C60H-DC, SW60-DC, C60NA-DC, C60PV-DC, iSW devices | 50 mm² Al terminal | 10 Nm |
| Accessories for iC120, DPN, DPN Vigi, C60H-DC, SW60-DC, C60NA-DC, C60PV-DC, iSW devices | Screw-on connection for ring terminal | 2 Nm |
| Electrical auxiliaries for iC120, DPN, DPN Vigi, ID, C60H-DC, SW60-DC, C60PV-DC, C60NA-DC devices | Indication and tripping auxiliaries | 1 Nm |
| P25M Load protection Motor starter protection | P25M | 1.7 Nm |
| P25M Load protection Motor starter protection | Electrical auxiliaries | 1.4 Nm |
| iPRD surge arresters | iPRD | 3.5 Nm |
| iQuick PRD Withdrawable surge arrester | iQuickPRD | 2.5 Nm |
| iPRD-DC surge arresters | iPRD-DC | 2 Nm |
| REDs, REDtest Earth leakage protection Automatic recloser | REDs, REDtest N, L | 2 Nm |
| REDs, REDtest Earth leakage protection Automatic recloser | REDs, REDtest Aux | 0.4 Nm |
| RED A type 30mA Earth leakage protection Automatic recloser | RED A type 30 mA 25 to 40A | 2 Nm |
| Reflex iC60H Control, remote control Integrated control circuit breakers | Power Connection 10 to 25 A | 2 Nm |
| Reflex iC60H Control, remote control Integrated control circuit breakers | Power Connection 40 to 63A | 3.5 Nm |
| Reflex iC60H Control, remote control Integrated control circuit breakers | Power supply (N/P) & Inputs (Y1/Y2) | 1 Nm |
| Reflex iC60H Control, remote control Integrated control circuit breakers | Outputs (O/C, auto/OFF) | 0.7 Nm |
| ARA automatic reclosers For iC60 CB and iID RCCB | Power supply (N/P) & Inputs (Y1/Y2) | 1 Nm |
| ARA automatic reclosers For iC60 CB and iID RCCB | Outputs (OF/Locked) | 0.7 Nm |
| RCA remote controls For iC60 CB | Power supply (N/P) & Inputs (Y1/Y2) | 1 Nm |
| RCA remote controls For iC60 CB | Outputs (OF) | 0.7 Nm |
| Acti 9 smartlink | Analog connector | 0.8 Nm |
| Acti 9 smartlink | Power supply connector | 0.8 Nm |
| Acti 9 smartlink | Modbus connector | 0.8 Nm |
| iCT contactors | iCT Control Circuit | 0.8 Nm |
| iCT contactors | iCT Power Circuit 16 and 25 A | 0.8 Nm |
| iCT contactors | iCT Power Circuit 40 to 63 and 100 A | 3.5 Nm |
| iCT contactors | iACTs, iACTp, iACTc, iATEt | 0.8 Nm |
| iCT contactors | iACT24 Power supply (N/P) & Input (Y1/Y2) | 1 Nm |
| iTL impulse relays | iTL, iTLi, iTLc, iTLm, iTLs, iETL 16 A Power and Control | 1 Nm |
| iTL impulse relays | iTL, iETL 32 A Control | 1 Nm |
| iTL impulse relays | iTL, iETL 32 A Power | 1.2 Nm |
| iTL impulse relays | iATLs, iATLc, iATLc+s, iATLc+c, iATLm, iATEt, iATL4, iATLz | 1 Nm |
| iTL impulse relays | ATL24 Power supply (N/P) & Inputs (Y1/Y2) | 1 Nm |
| iTL+ high-performance impulse relays | TL+ | 1 Nm |
| iIL indicator lights | iIL | 1 Nm |
| iPB pushbuttons | iPB | 1 Nm |
| iSW switches | iSW 40 to 125 A | 3.5 Nm |
| iSW switches | iCF | 1 Nm |
| iSW switches | iSW 22 and 32 A | 1.2 Nm |
| iSW switches | OF iSW | 1.2 Nm |
| iSSW linear switches | iSSW | 1 Nm |
| iTR transformers | iTR | 0.5 Nm |
| iSO bells and iRO buzzers | iSO | 1.3 Nm |
| STI isolatable fuse carriers | STI | 2 Nm |
| SBI fuse holder with indicator light | 14 x 51 mm & 22 x 58 mm | 3.5 Nm |
| DIN rail selector switches iCMB, iCMD, iCME, iCMC, iCMV and iCMA | iCMB, iCMD, iCME, iCMC, iCMV and iCMA | 0.35 Nm |
| Timers MIN, MINs, MINp and MINt | MIN, MINs, MINp, MINt | 1.2 Nm |
| Time switches IHP, IH, IHH and ITA | IHP, IH, IHH and ITA | 1.2 Nm |
| Twilight switches IC100, IC2000P+ | IC100, IC2000P+ | 1.2 Nm |