Initial values from a converted Concept application does not get transferred to the PLC.
The reason this occurs is due to the checkbox for 'Initialize %MWi' not being selected in the CPU configuration.
To resolve the issue:
To resolve the issue:
- Open the CPU configuration window.
- Select the checkbox 'Initialize %MWi'.
- Rebuild the application.
- Retest.