How to configure EIP buscycle with BMED581020 (IEC 61499)

Context: Example BusCycle EIP configuration (IEC 61499) between BMED581020 and BMEP586040.
EIP configuration BMED581020

BMED581020 EIP configuration buscycle

BusCycleTime must be greater than RPI O -> T + RPI T -> O

Example:
BusCycleTime (80ms) >> RPI O -> T (30ms) + RPI T -> O (30ms)

Note: if there are several devices, take the highest RPI O -> T and RPI T -> O.