PowerLogic PM5000 Series meter displays exclamation marks around Ethernet configuration values
Issue
When configuring a static IPv4 address from the meter front display, exclamation marks appear around the IPv4 address, subnet mask, and default gateway values after attempting to accept the configuration.
The meter does not accept or retain the new Ethernet settings and may return to the previous working configuration.
PM5000 does not accept a static IPv4 configuration
Product Line
PowerLogic PM5000 Series
Environment
PowerLogic PM5000 Series meter
Ethernet communication
Static IPv4 configuration from the meter front display
Cause
The exclamation marks indicate that the entered Ethernet configuration contains invalid or incompatible network values.
This can occur when the IPv4 address and default gateway are not within the same subnet defined by the subnet mask.
Example:
- IPv4 address: 172.21.86.19
- Subnet mask: 255.255.255.0
- Default gateway: 172.21.79.1
With the subnet mask 255.255.255.0, the meter IP address belongs to the 172.21.86.0/24 network. The gateway belongs to the 172.21.79.0/24 network and is outside the meter’s local subnet.
As a result, the meter displays exclamation marks around the Ethernet values and does not accept the configuration.
Resolution
- Double-check the IPv4 address, subnet mask, and default gateway entered on the meter.
- Confirm that the meter IP address and gateway are within the same subnet.
- If the settings do not match, obtain the correct network information.
- Enter the corrected settings and confirm that the meter accepts the configuration without displaying exclamation marks.
- Verify communication by pinging the meter from a computer with a compatible IP address.
Note:
Do not upgrade or downgrade the meter firmware solely because exclamation marks appear around the Ethernet values. First verify that the IPv4 address, subnet mask, and default gateway form a valid network configuration.