How to transfer the application program from Primary to Standby PLC automatically in Quantum Hot Standby System.
Sense the Status word bit %SW61.4 for program mismatch in both controllers. When true make %SW60.5 high for
program transfer from primary to standby PLC.

QUANTUM.PNG