How can we help you today?

Is it necessary to disconnect Micrologic while doing insulation or dielectric test with Masterpact NW ACB.

Yes, it is necessary to disconnect the micrologic before going for insulation or dielectric test on ACB.
The reason is that with LR plug is connected to the Micrologic, it makes internal connections between PCB
inside the Micrologic, whereas with the LR plug is disconnected; it disconnects PCBS inside the Micrologic.

If the Dielectric test is done with the LR plug connected, the high voltage value will damage the micrologic.

Due to same reason there is self-stick warning label on the Micrologic.
(The text is WARNING DISCONNECT RATING PLUG BEFORE DIELECTRIC TEST).

Schneider Electric India

Explore more

Discuss this topic with experts

Visit our community and get advice from experts and peers on this topic and more

Explore more

Need help?

Product Selector

Quickly and easily find the right products and accessories for your applications.

Get a Quote

Start your sales enquiry online and an expert will connect with you.

Where to buy?

Easily find the nearest Schneider Electric distributor in your location.

Help Centre

Find support resources for all your needs, in one place.