Power Fail Error (Power Fail Data lost) A Power Fail Error occurs after switching on the drive. ( failure: 5446 )

Goals and Symptoms

Power Fail Error (Power Fail Data lost)
A Power Fail Error occurs after switching on the drive.
( failure: 5446 )

Causes and Fixes

Analysis: This problem occurs only, if a Eeprom write command is just active, when the power fail case is activated. This can happen when e.g. the fault history is just written to the Eeprom.

Possible use case: Switching off a drive by switching off the mains while amplifier is active
What happens: a fault is created (undervoltage) and the drive starts to store the error history in the Eeprom just when the 24V undervoltage situation occurs !

This problem occurs on all drives with the follwoing official versions:

LXM32C V01.04.04
LXM32A V01.04.04
LXM32/M V01.02.04
With older versions, there is no problem.

The problem is fixed with the following versions:
LXM32C V01.06.05
LXM32A V01.06.05
LXM32/M V01.04.05


Legacy KB System (APS) Data: RESL203565 V1.0, Originally authored by BeBr on 10/04/2010, Last Edited by BeBr on 10/04/2010
Related ranges: Lexium 32
Comment M.Vetterer please delete the article! Not needed any more.

Schneider Electric India

Users group

Discuss this topic with experts

Visit our community and get advice from experts and peers on this topic and more
  • Products Documentation
  • Software Downloads
  • Product Selector
  • Product Substitution and Replacement
  • Help and Contact Centre
  • Where to buy
  • Get a Quote
  • Find our Offices
  • Schneider Electric Community
  • Careers
  • Company Profile
  • Report a misconduct
  • Accessibility
  • Newsroom
  • Investors
  • EcoStruxure
  • Job Search
  • Blog
  • Contact support - +1800-103-0011
  • Price List
  • Privacy Policy
  • Cookie Notice
  • Terms of use
  • Change your cookie settings