What is the Modubs Register for Digital Input 1 (DI1) for a 7650

Issue

What Modbus register should be used to read Digital Input 1 (DI1) on an ION7650 meter?

Product Line

PowerLogic ION7650

Environment

Modbus (RTU or TCP)

ION Setup or ION Designer

External SCADA/PLC/RTU

Cause

Not all ION modules have a hard‑coded Modbus register. DI1 on the ION7650 is one such case.

Resolution

  • Map the DI1 module’s State output to a Modbus Slave register, then read that Modbus holding register from your master.

Note

ION7650 is discontinued, the recommended Schneider Electric replacement  is ION9000 series.