Is it possible to have a READ_REG or WRITE_REG function block bridge Ethernet to Modbus through a TSXETG100?
Yes. A READ_REG or WRITE_REG block can reach a serial Modbus device through a TSXETG100 gateway, using the block's ADDRFLD parameter to carry both the gateway's address and the target device's ID.
How it works:
ADDRFLD is a 5-word array (WordArr5). Its 5 words are split across two roles:
| Word(s) | Contents |
| Word 1 (high byte) | Physical slot of the Ethernet module in the local rack |
| Word 1 (low byte) | The target device's Local ID, as configured in the TSXETG100's Device List |
| Words 2–5 | TSXETG100's IP address, one octet per word |
Example: to reach a device with Local ID 5 through a TSXETG100 at IP 192.168.40.7, with the Ethernet module in slot 4:
- Word 1 =
16#0405(hex04= slot 4, hex05= Local ID 5) - Words 2–5 =
192,168,40,7
Note : The low byte of word 1 is the device's Local ID as set up on the TSXETG100 itself (Setup > Device List, Slave mode) — not necessarily its real serial slave address. The gateway's Device List maps each Local ID to a Remote ID (the device's actual address on the serial line). Check the gateway's Device List to confirm which Local ID has been assigned to the device you're targeting
Released for: Schneider Electric India
Explore more
Range:
Explore more
Range:
Need help?
Product Selector
Quickly and easily find the right products and accessories for your applications.
Get a Quote
Start your sales enquiry online and an expert will connect with you.
Where to buy?
Easily find the nearest Schneider Electric distributor in your location.
Help Centre
Find support resources for all your needs, in one place.