How can we help you today?
How to configure the I/O configuration for PM850 via. front display panel for Analogue output 1 --> Real Power & Analogue Output 2 --> Average current
Refer below steps to configure the Analogue output channels;
1. Navigate to setup tab of Analogue output configuration (Maint -->Setup --> A/O)
2. Select AO1
2. Enter 4-20 mA in mapping
3. Enter the register number for the parameter which you want to assign to Analogue Output 1 (AO1) i.e. 1143 for Real Power
4. Enter Lower and Upper values for engineering scaling to be configured in PLC/DCS.
5. Repeat the steps 1 to 3 for AO2 configuration
6. Enter the register number for the parameter which you want to assign to Analogue Output 2 (AO2) i.e. 1105 Current, 3-Phase Average
Released for: Schneider Electric India
Need help?
Product Selector
Quickly and easily find the right products and accessories for your applications.
Get a Quote
Start your sales enquiry online and an expert will connect with you.
Where to buy?
Easily find the nearest Schneider Electric distributor in your location.
Help Centre
Find support resources for all your needs, in one place.