undefined [object Object]
{}

Our Brands

Impact-Company-Logo-English Black-01-177x54

Welcome to the Schneider Electric Website

Welcome to our website.
How can we help you today?
Do we need to do Dielectric & insulation test for Altivar 71 drives.
We made a Dielectric & insulation test during the final test after the manufacturing of ATV drives.So.no need to do these tests.
However, for information, please find the detail of dielectric test in attachment and Regarding Insulation resistance test, For all ATV ranges of drives should carry an insulation resistance test between power terminal (A) and ground @ 500VDC for 1 min. and should get value of >= 1 M OHM
Note: Power Terminal is same "A" as per the dielectric test.

Schneider Electric India

Attachment(s)
Dielectric test.zip [62.14 KB]
Explore more
Range:
Articles that might be helpful Users group

Discuss this topic with experts

Visit our Community for first-hand insights from experts and peers on this topic and more.
Explore more
Range: