How to enable and disable Output into bypass or Output out of bypass in SRC6KUXI models ?
To enable and disable Output into bypass or Output out of bypass in SRC6KUXI model, follow the below instructions:
• Input supply should be on to the UPS.
• Turn on the UPS [display should be on].
• Click on ‘Enter’ button for Main Menu.
• Select the ‘Control’ option from Main Menu and enter on it.
• Inside the ‘Control’ option, select second option ‘Output Control’ and click enter on it.
• Enter down arrow button until you find the option ‘Output into bypass’: The bypass mode is enabled/ ‘Output out off bypass’: The bypass mode is disabled.
• Enter on the option as per the requirement to set the desired settings.
• Press Mute/Esc button twice to return to main screen.
• Input supply should be on to the UPS.
• Turn on the UPS [display should be on].
• Click on ‘Enter’ button for Main Menu.
• Select the ‘Control’ option from Main Menu and enter on it.
• Inside the ‘Control’ option, select second option ‘Output Control’ and click enter on it.
• Enter down arrow button until you find the option ‘Output into bypass’: The bypass mode is enabled/ ‘Output out off bypass’: The bypass mode is disabled.
• Enter on the option as per the requirement to set the desired settings.
• Press Mute/Esc button twice to return to main screen.
Released for: Schneider Electric India
Explore more
Range:
Explore more
Range:
Need help?
Product Selector
Quickly and easily find the right products and accessories for your applications.
Get a Quote
Start your sales enquiry online and an expert will connect with you.
Where to buy?
Easily find the nearest Schneider Electric distributor in your location.
Help Centre
Find support resources for all your needs, in one place.