How to enable and disable Output into bypass or Output out of bypass in SRC6KUXI models ?

To enable and disable Output into bypass or Output out of bypass in SRC6KUXI  model, follow the below instructions:

• Input supply should be on to the UPS.
• Turn on the UPS [display should be on].
• Click on ‘Enter’ button for Main Menu.
• Select the ‘Control’ option from Main Menu and enter on it.
• Inside the ‘Control’ option, select second option ‘Output Control’ and click enter on it.
• Enter down arrow button until you find the option ‘Output into bypass’: The bypass mode is enabled/ ‘Output out off bypass’: The bypass mode is disabled.
• Enter on the option as per the requirement to set the desired settings.
• Press Mute/Esc button twice to return to main screen.