What is the meaning of ASC scaling for the setting of Analogue output of ATS48 Soft Starter.
Refer to attached document; there is a formula for AO assignment.

For motor current, please see below: ---

Is = 20ma * [X(%) /ASC].

Where “X” represents the percentage reading compared to the nominal value selected (motor nominal current, nominal torque ...).

Example:

AO (Analog Output) => OCr : Motor current

O4 (Configuration of the type of signal supplied by output AO) => -020:0-20mA signal

ASC range is from 50 to 500% and factory setting is 200.

And for Example: if you program In = 120A as per Motor detail then X will be equal to 100% if 120A read by ATS48 [means=>120 A monitored by Motor Current (LCr) parameter from displayed menu (SUP)].

So, if ASC = 200%.

Then AO will be :=> 20ma * [X(%) /ASC].

=> 20mA *[100/200] = 10 mA

Schneider Electric India

Attachment(s)
ATS48_AO Analog output assignment calculation.zip [23.14 KB]
Explore more
Range:
Users group

Discuss this topic with experts

Visit our community and get advice from experts and peers on this topic and more
Explore more
Range:
  • Products Documentation
  • Software Downloads
  • Product Selector
  • Product Substitution and Replacement
  • Help and Contact Centre
  • Where to buy
  • Get a Quote
  • Find our Offices
  • Schneider Electric Community
  • Careers
  • Company Profile
  • Report a misconduct
  • Accessibility
  • Newsroom
  • Investors
  • EcoStruxure
  • Job Search
  • Blog
  • Contact support - +1800-103-0011
  • Privacy Policy
  • Cookie Notice
  • Terms of use
  • Change your cookie settings