How Firmware can be upgraded for BMEXBP••00 rack .
We can upgrade the BME XBP ••00 rack firmware by downloading a new firmware version with Unity Loader through the CPU or a BME CRA 312 •0 module.
The firmware download can be performed by connecting to either of the following:
Refer to the CPU firmware upgrade procedure for a description of the download procedure. Also make sure the necessary security permission should be enabled.
Upgrade Procedure :
1. Install Unity Loader software provided with Unity Pro.
2 Connect the PC that is running Unity Loader to the CPU.
3 Launch Unity Loader.
4 Click Firmware tab.
5 In the PC list box, select the .ldx file that contains the firmware file.
6 When connected with Ethernet, check that the MAC address indicated in the PLC box corresponds to the MAC address marked on the CPU.
7 Check that transfer sign is green to allow transfer from PC to CPU.
8 Click Transfer
9 Click Close
Firmware :
The firmware file is included in a *.ldx file.
Troubleshooting :
If the rack power supply is turned off during the upgrade procedure, the backplane firmware remains on the version embedded before the upgrade procedure.
The firmware download can be performed by connecting to either of the following:
- The CPU mini-B USB connector
- The CPU Service port
- The Ethernet network
Refer to the CPU firmware upgrade procedure for a description of the download procedure. Also make sure the necessary security permission should be enabled.
Upgrade Procedure :
1. Install Unity Loader software provided with Unity Pro.
2 Connect the PC that is running Unity Loader to the CPU.
3 Launch Unity Loader.
4 Click Firmware tab.
5 In the PC list box, select the .ldx file that contains the firmware file.
6 When connected with Ethernet, check that the MAC address indicated in the PLC box corresponds to the MAC address marked on the CPU.
7 Check that transfer sign is green to allow transfer from PC to CPU.
8 Click Transfer
9 Click Close
Firmware :
The firmware file is included in a *.ldx file.
Troubleshooting :
If the rack power supply is turned off during the upgrade procedure, the backplane firmware remains on the version embedded before the upgrade procedure.
Released for: Schneider Electric India
Explore more
Range:
Explore more
Range:
Need help?
Product Selector
Quickly and easily find the right products and accessories for your applications.
Get a Quote
Start your sales enquiry online and an expert will connect with you.
Where to buy?
Easily find the nearest Schneider Electric distributor in your location.
Help Centre
Find support resources for all your needs, in one place.