Segment Invalid RIO Drop Error during conversion of Proworx to Unity Pro with Quantum ERIO.
To overcome the Invalid drop error for converted application, follow the below steps:
Right Click on Segment>> properties>>Remote I/O tab>> Set read/write value to 0 or 1.
ERIO will not work with the RIO option and this remote drop may use in S908 architecture .
You may use IU_ERIO function block to do Immediate remote drop I/O Access.
Right Click on Segment>> properties>>Remote I/O tab>> Set read/write value to 0 or 1.
ERIO will not work with the RIO option and this remote drop may use in S908 architecture .
You may use IU_ERIO function block to do Immediate remote drop I/O Access.